Different Frequency Automatic Dielectric Loss Tester

본문 바로가기


Home > Product > Different Frequency Automatic Dielectric Loss Tester
Product
Different Frequency Automatic Dielectric Loss Tester
Posting date : Jun 24, 2010
Membership
Free Member Scince Jun 24, 2010
Keyword :
Category
Contact
          0 likes     
Product Detail
Company Info
 
Quick Detail
Place of Origin
HS-CODE
84-
Package & Delivery Lead Time
Detailed Description
1.1General introduction APGS different frequency automatic dielectric loss tester is a high-precision instrument, which can be applied to automatically measure electrical loss tangent ( ) and capacitance of all kinds of high voltage electrical equipments' on the spot of power plants, substations etc. 1.2 Technical Index 1. Condition of Use -5℃~40℃, RH<80% 2. Power Source AC 110V±10% Without Frequency Limit 3. High Voltage Output Range 1KV~10KV, every 1KV Precision 5% Maximum Current 140mA Capacity 1000VA 4. Self-Excited Power Voltage Range AC 0V~30V; Frequency 45Hz /55Hz Maximum Current 15A 5. Definition tgδ: 0.001% ; Cx: 0.1PF 6. Measuring Range tgδ Without Limit 10kV 1kV CVT Test 7. Size 470mm(L) ×320mm(W)×390mm(H) 8. Weight: 30kg

ECROBOT CO., Ltd, Business Registration Number : 220-88-71747, CEO J.W.Park, TEL : +82-2-552-7676, E-mail : E-mail : Contact us
Address : (Hwanghwa B/D 11F, Yeoksam-dong)320, Gangnam-daero, Gangnam-gu, Seoul, South Korea
About Us Privacy Policy Terms of use Copyright © 2000-2026 ECROBOT.COM. All rights reserved.