No.
|
Parameter name
|
Unit
|
Value
|
1
|
Rated voltage
|
kV
|
12
|
2
|
Rated current
|
A
|
630
|
3
|
Rated frequency
|
Hz
|
50
|
4
|
Rated making current
|
kA
|
6.3
|
5
|
Rated breaking current
|
kA
|
5.04
|
6
|
Limiting breaking current
|
kA
|
6.3
|
7
|
Rated short-time withstand current
|
kA
|
6.3
|
8
|
Rated short-time withstand voltage
|
kV
|
42
|
9
|
Rated lighting impulse voltage
|
kV
|
75
|
10
|
Circuit resistance at lowest rated contacts force
|
μΩ
|
≤80
|
11
|
Electrical life
|
Times
|
250000
|
12
|
Mechanical life
|
times
|
500000
|
13
|
Closing force due to bellows and atmosphere
|
N
|
70±20
|
14
|
Force required to hold contacts open at full stroke
|
N
|
100±30
|
15
|
Limiting abrasion of contacts
|
mm
|
3
|
16
|
Internal gas pressure
|
Pa
|
≤1.33×10-3
|
17
|
Storage life
|
years
|
20
|