Diesel Generator Set Data
Set Type: XG-200GF
Prime Power: 200KW/250KVA
Rated Current: 328(A)
Rated Frequency: 50(Hz)
Start-up time: 5~6(s)
Power Factor: 0.8(Lag)
Rated Voltage: 400/230(V)
Standard Features
1. Engine: VOLVO TAD733GE
2. Radiator 50℃ max
3. Fans are driven by belt, with safety guard
4. 24V charge alternator
5. Dry type air filter, fuel filter, oil filter
6. Alternator: single bearing alternator
7. IP23, insulation class H/H
8. Main line circuit breaker
9. Standard control panel
10. Absorber
11. Muffler
12. User manual
Diesel Engine Data | ||
Manufacturer: | VOLVO | |
Model: | TAD733GE | |
Standby/Prime Power: | 196KW/179KW | |
Rated Speed: | 1500(r/min) | |
Cycle: | 4 stroke | |
Cylinder Arrangement: | 6 in line | |
Displacement: | 7.15L | |
Bore and Stroke: | 108*130(mm) | |
Compression Ratio: | 18:1 | |
Governor Type: | Electronic | |
Start battery voltage: | 24V DC | |
Air Intake System | ||
Air Intake System: | Turbo, Air/Air Cooling | |
Max Intake Restriction: | 3.5kpa | |
Burning Capacity: | 12.4m3/min | |
Air Flow: | 222 m3/min | |
Exhaust System | ||
Exhaust Gas Flow: | 37.2 m3/min | |
Exhaust Temperature: | 530℃ | |
Max Back Pressure: | 3kPa | |
Fuel System | ||
Fuel System: | Directly Injection Fuel System, Bosch Pump | |
100%( Prime Power) Load: | 196g/kwh | |
50%( Prime Power) Load: | 211g/kwh | |
Oil System | ||
Total Oil Capacity: | 29L | |
Oil Consumption: | ≤0.09L/h | |
Engine Oil Tank Capacity: | 31L | |
Oil Pressure at Rated RPM: | 480kPa | |
Cooling System | ||
Cooling Way: | Water-cooled | |
Total Coolant Capacity: | 37.1L | |
Thermostat: | 87-102℃ | |
Max Water Temperature: | 105℃ | |
Alternator Data | ||
Manufacturer: | STARLIGHT/STAMFORD/SIEMENS/MARATHON/ENGGA /KEPU | |
Excitation Mode: | Brushless and self- exciting | |
Number of phase and Access Act: | 3-phase 4-wire | |
Connecting Type: | "Y" type connecting | |
Alternator Capacity: | 250KVA | |
Alternator Efficiencies: | 95% | |
Overload: | (PRP)110% load can run 1h | |
Protection Level: | IP22-IP23 | |
Insulation Class, Temperature Rise: | H/H | |
Telephone Influence Factor (TIF): | <50 | |
THF: | <2% | |
Voltage Regulation, Steady State: | ≤±1% | |
Air Cooling Flow: | 0.514m3/s | |
Altitude: | ≤1000m |